Philvolt

Philvolt Solar Guide

Can an 18-Unit Cassette Aircon Office Run Entirely on Rooftop Solar?

Can a 3-storey, 1,200 sqm Philippine office with 18 cassette aircons run entirely on rooftop solar? See the kWp, roof area, and offset math here.

Not entirely, and here's the math: an 18-unit, 90-ton cassette aircon load on a 400 sqm building footprint needs roughly 90 kW of cooling capacity, but a flat roof that size, after access ways and equipment space, only fits about 40 to 50 kWp of panels. At Philippine sun hours, that system covers an estimated 30 to 40 percent of daytime consumption, a meaningful net-metering offset, not a full off-grid replacement.

How Much Power 18 x 5-Ton Cassette Aircons Actually Draw

Start with the cooling load, not the floor area. Eighteen 5-ton cassette units add up to 90 tons of cooling capacity. As a planning rule of thumb, commercial cassette units draw somewhere around 0.8 to 1.2 kW of electricity for every ton of cooling, depending on whether the units are inverter-type or fixed-speed, so the full bank of 18 units could pull anywhere from roughly 70 kW to over 100 kW if every unit ran at full output at the same moment. In practice, aircon units cycle on and off to hold a setpoint, so not all 18 run at 100 percent simultaneously; applying a typical diversity (coincidence) factor of around 0.7 brings the realistic peak draw down to an estimated 65 to 70 kW. On top of that, a 3-storey, 1,200 sqm office building (400 sqm per floor) carries lighting, plug loads, and elevators, which for a general office in the Philippines typically adds another 15 to 25 watts per square meter, or roughly 18 to 30 kW. Added together, a realistic business-hours peak demand for this building lands in the neighborhood of 85 to 100 kW. That number, not the building's floor area, is the real target a solar-plus-battery system has to be sized against, and it is the first thing any solar proposal for this building should state clearly before quoting panel counts.

Why Roof Area Is the Real Ceiling on System Size

A 3-storey building with 400 sqm per floor does not have 1,200 sqm of usable roof. Unless the design steps back at each level, the rooftop is limited to roughly the footprint of a single floor, so the solar array has about 400 sqm to work with, not the building's total floor area. Usable roof space is smaller still once access ways, water tanks, exhaust vents, and fire-code clearances are subtracted; a commonly used planning assumption is that 70 to 80 percent of a flat commercial roof is actually available for panels, which brings this building's usable area down to roughly 280 to 320 sqm. Commercial rooftop solar installations typically need about 6 to 7 sqm of roof per kWp of installed capacity once panel spacing, tilt, and walkway clearances are accounted for. Dividing 280 to 320 usable sqm by that figure gives a realistic ceiling of approximately 40 to 50 kWp of solar that can physically be mounted on this roof. That ceiling matters because it is well below the 85 to 100 kW peak demand calculated from the aircon and office load, which is the core reason a building with this footprint and this aircon load cannot be powered entirely by its own rooftop, regardless of how efficient the panels are.

What a 40-50 kWp System Actually Produces in Philippine Sun Hours

The Philippines averages roughly 4.5 to 5 peak sun hours per day, meaning a solar array produces at its rated output for the equivalent of about 4.5 to 5 hours daily, even though the sun is up for 10 to 12 hours. After accounting for system losses such as inverter efficiency, wiring, soiling, and temperature derating (commonly estimated at 15 to 20 percent for a well-designed system), a 40 to 50 kWp array in the Philippines can be expected to generate roughly 150 to 190 kWh on an average clear day. Compare that to the building's own daytime consumption: at an estimated average running load of 50 to 60 kW across a typical 10-hour operating day (lower than the 85 to 100 kW peak because not everything runs at maximum continuously), the building could consume somewhere around 500 to 600 kWh on a typical weekday. Set side by side, the rooftop array's output covers roughly 25 to 35 percent of that daily consumption. This is a meaningful and financially worthwhile offset under net metering, but it is not close to covering the building's full daytime electricity needs, let alone powering it through the evening hours when aircon usage can still be high but the sun has set.

Why 'Entirely on Solar' Usually Means Hybrid, Not Off-Grid, at This Load

Going fully off-grid would mean sizing a battery bank large enough to cover the gap between what the 40 to 50 kWp roof can generate and what an 85 to 100 kW peak, 500 to 600 kWh per day building actually uses, including on cloudy and rainy days when Philippine solar output can drop by 40 percent or more. At this building's scale, that battery capacity requirement runs into the hundreds of kWh, which is a very different capital outlay than the solar array itself and is rarely the first step recommended for a commercial building of this size. The more common and more cost-effective path in the Philippines is a grid-tied system under the net metering framework established by the Renewable Energy Act (RA 9513) and implemented through the local distribution utility: the rooftop array offsets daytime consumption directly, any excess generation is exported to the grid for bill credit, and the grid continues to supply the building during early morning ramp-up, cloudy stretches, and all nighttime load. For a building with this aircon-heavy load profile and this roof footprint, a grid-tied net-metered system sized to the 40 to 50 kWp roof ceiling is the realistic recommendation, with battery storage treated as an optional add-on for specific priority circuits rather than a requirement for full building coverage.

What Would Change the Math for This Building

Three factors move the numbers in the previous sections. First, switching from fixed-speed to high-efficiency inverter-type cassette units can lower the kW-per-ton draw toward the lower end of the 0.8 to 1.2 kW/ton range used above, which directly reduces both the peak demand figure and the daily consumption estimate. Second, shifting non-essential heavy loads (pre-cooling, equipment testing, non-urgent charging) into midday hours when solar output peaks improves how much of the array's generation is actually used on-site rather than exported, which is usually the more valuable outcome under net metering. Third, if the building's design allows mounting panels on a canopy, carport, or adjacent structure rather than relying solely on the roof footprint, the 40 to 50 kWp ceiling calculated above can be raised, which is often the single biggest lever available once the roof itself is maxed out. None of these changes make a 90-ton, 1,200 sqm building fully self-sufficient on solar alone, but each one narrows the gap between what the roof can generate and what the building actually consumes, which is the number that ultimately determines the size of the electricity bill, not whether the system is labeled 'entirely solar.'

Frequently Asked Questions

1

Can a commercial building in the Philippines run completely off-grid on rooftop solar alone?

For a small, low-load building, yes, it is physically possible with enough roof area and battery storage. For a building with a heavy, continuous load like 18 cassette aircons on a limited roof footprint, going fully off-grid would require a battery bank sized in the hundreds of kWh to cover nighttime and cloudy-day gaps, which is a much larger investment than the solar array itself. In the Philippines, a grid-tied system under the net metering framework is the more common and more cost-effective approach for buildings this size, offsetting a meaningful share of daytime consumption while the grid continues to cover the rest.

2

Does a 3-storey building's roof give you 3 floors' worth of solar panel space?

No. Unless the upper floors step back from the one below, the roof is limited to roughly the footprint of a single floor, in this case about 400 sqm, not the building's combined 1,200 sqm of total floor area. After subtracting access ways, equipment, and clearance space, usable roof area for solar is typically 70 to 80 percent of that footprint, which is the figure that should be used when estimating how much solar capacity a multi-storey building can actually host.

3

How many kW does an 18-unit, 5-ton cassette aircon bank draw?

As a planning estimate, commercial cassette units draw roughly 0.8 to 1.2 kW of electricity per ton of cooling depending on efficiency, so 18 units at 5 tons each (90 tons total) could draw 70 to over 100 kW if every unit ran at full output simultaneously. Because aircon units cycle to hold temperature rather than running at 100 percent continuously, a diversity factor of around 0.7 is commonly applied, bringing the realistic peak draw down to roughly 65 to 70 kW. An actual load audit on the specific unit models installed will give a more precise figure than this estimate.

4

What is net metering and would it apply to a building this size?

Net metering, established under the Philippine Renewable Energy Act (RA 9513), lets a solar system owner export excess daytime generation to the grid in exchange for a bill credit, while still drawing from the grid when solar output is not enough to cover consumption. It applies to commercial buildings as well as residential ones and is the standard framework for grid-tied solar in the Philippines, including for a building with a large aircon load that cannot be fully covered by its own roof capacity.

5

How much does cloud cover affect solar output for an aircon-heavy building?

Philippine solar output can drop by an estimated 40 percent or more on heavily overcast or rainy days compared to a clear-sky day, which is exactly when aircon load tends to stay just as high since humidity, not just heat, drives cooling demand. This is the main reason a grid-tied (not off-grid) setup is the realistic choice for a building with a continuous aircon load: the grid absorbs the shortfall on low-sun days without requiring an oversized, expensive battery bank sized for worst-case weather.

6

Is it worth getting a load audit before sizing a rooftop solar system for this kind of building?

Yes. The estimates in this article use industry-standard planning rules of thumb (kW-per-ton draw, roof area per kWp, Philippine peak sun hours) because the actual numbers depend on the specific aircon models, their efficiency ratings, the building's real roof layout, and its actual hourly consumption pattern. A site-specific load audit replaces these estimates with measured figures and is the recommended next step before any system is quoted or installed.

Ilan ang matitipid mo?

I-upload ang Meralco bill mo, makakakuha ka ng real system size at price range sa 60 segundo.